• CSCD核心库收录期刊
  • 中文核心期刊
  • 中国科技核心期刊

Electric Power Construction ›› 2016, Vol. 37 ›› Issue (4): 124-130.doi: 10.3969/j.issn.1000-7229.2016.04.019

Previous Articles     Next Articles

Correction Control Strategy of Islanded Power Grid after Separation

SONG Honglei1, LI Xiaofei2, WU Junyong3,HU Jialin4, WANG Zhenming1   

  1. 1.State Grid Corporation of China AC Construction Branch, Beijing 100052, China;2. NARI Group Corporation State Grid Electric Power Research Institute, Nanjing 21106, China;3. School of Electrical Engineering, Beijing Jiao Tong University, Beijing 100044, China;4. School of Electrical and Electronic Engineering, North China Electric Power University, Beijing 102206, China
  • Online:2016-04-01

Abstract:

After the implementation of controlled islanding on unstable system, the separation surfaces split the whole system into two or more power islands. It is necessary that effective correction control measures are adopted to ensure the stable operation of each island. This paper proposes rapid real-time correction control strategy based on the bidirectional power flow tracing algorithm and DC flow algorithm of separation surface. Through the power flow tracing algorithm of separation surfaces, we obtain the adjustment object (generator and load) and quantity of island, and check the result with using DC flow algorithm to maintain transient stability under the condition that the islands satisfy the security and stability constraints. Simulations on the New England 39-bus system validate the effectiveness and flexibility of the proposed approach.

Key words:  separation island, correction control, power flow tracing algorithm, DC flow algorithm, load shedding and generator tripping

CLC Number: