• CSCD核心库收录期刊
  • 中文核心期刊
  • 中国科技核心期刊

Electric Power Construction ›› 2017, Vol. 38 ›› Issue (8): 80-.doi: 10.3969/j.issn.1000-7229.2017.08.011

Previous Articles     Next Articles

 Compensation Droop Control of MMC-MTDC Considering Line Voltage Drop
 

 DONG Hui,SONG Pinggang, ZHOU Zhenbang

 
  

  1.  (School of Electrical and Automation Engineering, East China Jiaotong University, Nanchang 330013, China)
     
  • Online:2017-08-01
  • Supported by:
     

Abstract:  ABSTRACT:   The traditional error control and droop control cannot achieve the floating control of power and voltage in MMC-MTDC (modular multilevel converter  based multi-terminal DC transmission systems). In order to make the system achieve the optimal operating state, this paper proposes the droop compensation control strategy. Firstly, we analyze the traditional control methods with fully considering the voltage drop caused by line impedance in the traditional control mode. Then, we compensate the voltage reference instruction of the droop curve for the voltage offset caused by the power deviation of the system. Finally, we construct a five terminal simulation model on PSCAD/EMTDC, and compare three control methods under the two conditions of steady state and transient state. The results show that the static deviation of power and voltage can be eliminated by changing the power of the system, and the voltage will not overshoot, which can ensure that the system is always running in the optimal state.

 

Key words:  , modular multilevel converter (MMC), multi-terminal DC transmission system (MTDC), droop control, line voltage drop, power command modification

CLC Number: