Electric Power Construction ›› 2017, Vol. 38 ›› Issue (8): 17-.doi: 10.3969/j.issn.1000-7229.2017.08.003

Previous Articles     Next Articles

DC System Impedance Scanning for MTDC

CUI Kangsheng1, WEN Jun1, ZHAO Xiaobin2, LI Rong1, YAN Han1, DUAN Ruimin3#br#   

  1. (1. School of Electrical and Electronic Engineering, North China Electric Power University, Beijing 102206, China分号2. State Key Laboratory of HVDC, Electric Power Research Institute, China Southern Power Grid, Guangzhou 510080, China分号3. Electric Power Research Institute, Yunnan Power Grid Co., Ltd., Kunming 650217, China)
  • Online:2017-08-01
  • Supported by:
     

Abstract: ABSTRACT:  DC system impedance scanning is one of the important means of harmonic suppression research and DC filter design on multi-terminal direct current (MTDC) transmission. This paper presents a DC system impedance scanning method for MTDC, in which the error from converter generated harmonic is excluded by improving impedance formula. Influence of various factors on the impedance scanning, such as amplitude, phase and frequency distribution of the injected harmonic source, is also studied. PSCAD/EMTDC simulation result shows that the presented method is effective and reliable for DC system impedance scanning of MTDC, which has reference value of DC engineering.

Key words: MTDC transmission, DC harmonic, resonant, impedance scanning, amplitude-frequency characteristics