ELECTRIC POWER CONSTRUCTION ›› 2015, Vol. 36 ›› Issue (8): 102-107.doi: 10.3969/j.issn.1000-7229.2015.08.017

Previous Articles     Next Articles

10  kV Combined Test Circuit Design with Impulse and Power Frequency Continuous Current

CHEN Sixiang1, SU Xingzhi1, KONG Huadong1,SUN Guanghui1, LIU Yijun1, QI Xiaojun2   

  1. 1. Foshan Power Supply Bureau of Guangdong Power Grid Co., Ltd., Foshan 528000, Guangdong Province, China; 2. Wuhan Shuiyuan Electrical Co., Ltd., Wuhan 430073,  China
  • Online:2015-08-01
  • Supported by:

    Project Supported by China Southern Power Grid Co.,Ltd (K-GD2013-0268).

Abstract:

To test the capability of 10 kV lightning protection device with series gaps to cut off the power frequency continuous current after the device breakdown by lightning, this paper designed a test loop in combination with impulse test and power frequency continuous current test. In order to generate power frequency continuous current with high amplitude under higher voltage, a LC series and parallel resonant circuit was used in which the parameters of each element were calculated and selected and their reasonable values were given. Finally, a synchronization control circuit was chosen to extract the impulse signal to conduct the power frequency continuous current circuit, which could realize the synchronization in impulse test and power frequency continuous current test. The calculation results show that the combined test circuit can generate 1.2/50 μs impulse waveform, and 50 Hz sinusoidal current wave with 100 ms oscillation, which can meet the requirement of testing the capability of lightning protection device with series gaps to cut off electric arc under power frequency continuous current after the device breakdown by lightning.

Key words: lightning protection device with series gaps, LC series and parallel resonant, power frequency continuous current, combined test, synchronization control