电力建设 ›› 2015, Vol. 36 ›› Issue (9): 73-77.doi: 10.3969/j.issn.1000-7229.2015.09.012

• 特高压直流输电技术专辑 • 上一篇    下一篇

特高压换流站800 kV交流滤波器小组断路器容性恢复电压仿真

申笑林1,马为民1,白光亚2,聂定珍1   

  1. 1.国网北京经济技术研究院,北京市102209;2.国家电网公司直流建设分公司,北京市 100052
  • 出版日期:2015-09-01
  • 作者简介:申笑林(1985),男,硕士,工程师,从事高压直流输电工程咨询和成套设计相关研究工作;; 马为民(1966),男,博士,高级工程师,从事高压直流输电工程咨询和成套设计相关研究工作;; 聂定珍(1961),女,硕士,高级工程师,从事高压直流输电工程咨询和成套设计相关研究工作;; 白光亚(1971),男,硕士,高级工程师,从事高压直流输电工程建设相关工作。

Simulation and Investigation on Capacitive Recovery Voltage of 800 kV AC Filter Sub-Bank Circuit Breaker in UHVDC Converter Station

SHEN Xiaolin1, MA Weimin1, BAI Guangya2, NIE Dingzhen1   

  1. 1.State Power Economic Research Institute, Beijing 102209, China;2.DC Construction Branch of State Grid Corporation, Beijing 100052, China
  • Online:2015-09-01

摘要:

特高压直流直接接入交流750 kV电网,对投切交流滤波器小组的断路器的耐压能力提出了严苛的要求,因此需要研究断路器的容性恢复电压水平。分析了交流滤波器小组断路器面临的各种交流故障工况,通过PSCAD软件建立了容性恢复电压的仿真计算模型,并以灵绍特高压直流工程为例计算得出了800 kV交流滤波器小组断路器的容性恢复电压最大值。仿真结果表明交流滤波器小组断路器的容性恢复电压由交流系统的短路水平和交流侧绝缘水平的影响决定,而且容性恢复电压超过了现有标准的要求,需研制适应工程需求的新型断路器。

关键词: 容性恢复电压, 交流滤波器, 断路器, 特高压直流

Abstract:

 The circuit breaker for switching AC filter is required the capacity of withstanding high voltage while the UHVDC direct accesses to 750 kV AC grid, So it is necessary to research the capacitive recovery voltage (CRV) of circuit breaker. This paper analyzed various AC fault scenarios of AC filter sub-bank circuit breaker, constructed the simulation calculation model of CRV by PSCAD software, and calculated the maximum value of CRV of 800 kV AC filter sub-bank breaker in the Lingshao UHVDC project. The simulation results show that the CRV of AC filter sub-bank breaker is determined by the short-circuit level of AC system and the AC-side insulator level, and the CRV exceeds the requirement of existing standards, so it is needed to develop new type of circuit breaker to meet the needs of engineering.

Key words: capacitive recovery voltage, AC filter, circuit breaker, UHVDC