• CSCD核心库收录期刊
  • 中文核心期刊
  • 中国科技核心期刊

ELECTRIC POWER CONSTRUCTION ›› 2015, Vol. 36 ›› Issue (9): 73-77.doi: 10.3969/j.issn.1000-7229.2015.09.012

Previous Articles     Next Articles

Simulation and Investigation on Capacitive Recovery Voltage of 800 kV AC Filter Sub-Bank Circuit Breaker in UHVDC Converter Station

SHEN Xiaolin1, MA Weimin1, BAI Guangya2, NIE Dingzhen1   

  1. 1.State Power Economic Research Institute, Beijing 102209, China;2.DC Construction Branch of State Grid Corporation, Beijing 100052, China
  • Online:2015-09-01

Abstract:

 The circuit breaker for switching AC filter is required the capacity of withstanding high voltage while the UHVDC direct accesses to 750 kV AC grid, So it is necessary to research the capacitive recovery voltage (CRV) of circuit breaker. This paper analyzed various AC fault scenarios of AC filter sub-bank circuit breaker, constructed the simulation calculation model of CRV by PSCAD software, and calculated the maximum value of CRV of 800 kV AC filter sub-bank breaker in the Lingshao UHVDC project. The simulation results show that the CRV of AC filter sub-bank breaker is determined by the short-circuit level of AC system and the AC-side insulator level, and the CRV exceeds the requirement of existing standards, so it is needed to develop new type of circuit breaker to meet the needs of engineering.

Key words: capacitive recovery voltage, AC filter, circuit breaker, UHVDC

CLC Number: