川藏联网工程复合材料电气设备地震模拟振动台试验研究

程永锋1,卢智成1,刘振林1,孙宇晗1,丁燕生2,易建山2,孟宪政1,鲁先龙1   

  1. 1.中国电力科学研究院,北京市 102401;2.川藏联网工程建设指挥部,成都市 610000
  • 出版日期:2015-03-01
  • 作者简介:程永锋(1969),男,博士,教授级高级工程师,主要从事输变电工程地基基础与防灾减灾的研究工作; 卢智成(1978),男,博士,高级工程师,主要从事电力设施抗震的研究工作; 刘振林(1987),男,硕士,工程师,主要从事电力设施抗震的研究工作; 孙宇晗(1984),男,硕士,工程师,主要从事电力设施抗震的研究工作; 丁燕生(1964),男,学士,高级工程师,主要从事输变电工程的建设与技术管理工作; 易建山(1968),男,学士,高级工程师,主要从事输变电工程的建设与技术管理的研究工作; 孟宪政(1986),男,学士,工程师,主要从事电力设施抗震的研究工作; 鲁先龙(1972),男,博士,高级工程师,主要从事输变电工程地基基础与防灾减灾的研究工作。
  • 基金资助:

    国家电网公司科技项目(5299001352u7)。

Experimental Study of Earthquake Simulation Shaking Table on Electrical Equipment of Composite Material for Sichuan-Tibet Interconnection Project

CHENG Yongfeng1, LU Zhicheng1, LIU Zhenlin1, SUN Yuhan1, DING Yansheng2, YI Jianshan2, MENG Xianzheng1, LU Xianlong1   

  1. 1. China Electric Power Research Institute, Beijing 102401, China; 2. Construction Headquarter of Project Grid Between
    Sichuan and Tibet, Chengdu 610000, China
  • Online:2015-03-01

摘要:

复合材料电气设备由于其具有质量小强度高的材料特点,已在部分变电站内推广应用,但对于复合材料电气设备的抗震性能,尤其对于其真型设备的地震模拟振动台的试验研究,各国学者研究较少。依托于川藏联网工程,在总结国内外复合材料电气设备抗震研究成果的基础上,结合我国已有电气设备抗震研究成果,开展了适用于复合材料电气设备抗震性能评估方法的研究,确定了复合材料电气设备振动台试验输入波形、波形峰值加速度以及设备抗震能力判定原则,采用此方法对800   kV高抗套管、220   kV GIS外绝缘套管、110   kV及220   kV避雷器分别进行地震模拟振动台试验,得到了设备的动力特性和地震响应。由试验结果可以看出,参与试验的复合材料电气设备应力均满足设计基本加速度为0.4 g的抗震要求。

关键词: 川藏联网工程, 电气设备, 抗震, 复合材料, 套管, 避雷器

Abstract:

 Electrical equipment of composite material has been applied in some substations, due to its characteristics of lighter quality and higher breaking strength. However, little research has been done in the seismic behavior of electrical equipment of composite material, especially for the experimental study of earthquake simulation shaking table. Based on the Sichuan-Tibet interconnection project, this paper summarized the researches on the seismic behavior of electrical equipment of composite material at home and abroad, and then studied its assessment method combined with the existing research on the seismic behavior of electrical equipment in China. Then, the input waveform, the peak acceleration and the judging principle of seismic ability also had been confirmed for the shaking table test of composite materials electric equipment. With using this method, 800   kV HV reactor bushing, 220  kV GIS external insulation bushing, 110   kV and 220   kV lightning arresters were tested respectively on earthquake simulation shaking table, and the dynamic characteristics and seismic response of the equipment were obtained. The test results show that the stresses on the tested electrical equipments of composite material all meet the seismic requirements of 0.4 g designed basic acceleration.