电力建设 ›› 2016, Vol. 37 ›› Issue (1): 131-136.doi: 10.3969/j.issn.1000-7229.2016.01.020

• 发电技术 • 上一篇    下一篇

风电机组箱式变压器低压侧雷电过电压仿真

满于维1,余光凯2,韦焕林1,常泰福1,张博2,鲁铁成2   

  1. 1.中电投广西金紫山风电有限公司,广西壮族自治区 桂林市 541100;2.武汉大学电气工程学院,武汉市 430072
  • 出版日期:2016-01-01
  • 作者简介:满于维(1989),男,高级工程师,主要从事风电场升压站、风电机组维护与检修工作; 余光凯(1991),男,硕士研究生,主要研究方向为电力系统过电压及防雷接地技术; 韦焕林(1988),男,工程师,主要从事风电场运行维护工作; 常泰福(1990),男,工程师,主要从事风电场设备维护与检修工作; 张博(1979),男,博士,副教授,主要从事电力系统过电压及仿真计算方面的研究工作; 鲁铁成(1953),男,博士,教授,博导,主要从事电力系统过电压方面的研究工作。

Box-Type Transformer Lightning Overvoltage Simulation at Low-Voltage Side in Wind Turbines

MAN Yuwei1, YU Guangkai2, WEI Huanlin1, CHANG Taifu1,ZHANG Bo2, LU Tiecheng2   

  1. 1. Guangxi Jinzishan Branch of China Power Investment Corporation, Guilin 541100, Guangxi Zhuang Autonomous Region, China;2. School of Electrical Engineering, Wuhan University, Wuhan 430072, China
  • Online:2016-01-01

摘要:

针对某高山风电场风机塔顶遭受雷击,造成风电机组塔外箱式变压器(简称箱变)损坏事故,分析了箱变低压侧雷电过电压产生的机理,根据风机-箱变系统防雷配置情况,建立了ATP-EMTP仿真模型。利用该模型计算了电涌保护器(surge protective device,SPD)接入时和脱开后箱变低压侧的电压,并分析了雷电流波形、幅值及接地网冲击接地电阻对箱变低压侧电压的影响,同时计算了低压侧短路后的工频续流。计算结果表明,SPD脱开后低压侧电压超过了箱变的冲击耐压值(12  kV),低压侧工频续流为4.50~8.75 kA。由于开关型SPD无法切断工频续流,提出将其更换为无续流的氧化锌避雷器,推荐避雷器型号为YH10W-0.8/3.0,并通过仿真计算进行了防雷效果验证。

关键词: 风电机组, 箱式变压器, 地电位升高, 雷电过电压, 工频续流, 电涌保护器(SPD)

Abstract:

Aimed at damage accidents of box-type transformer outside wind turbine when the top of wind tower being struck by lightning, an ATP/EMTP simulation model is established according to wind turbine-box type transformer system lightning protection, which is based on the mechanism analysis of the lightning overvoltage of box-type transformer at low-voltage side. We use this model to calculate the lightning overvoltage of box-type transformer at low-voltage side when surge protective device (SPD) is connected and disconnected, and analyze the influences of the waveform and peak of lightning current, impulse grounding resistance on the voltage on the low voltage side of box-type transformer. Meanwhile, we calculate the power frequency current after the low-voltage side short circuit of transformer. The calculation result shows that the potential differences of low-voltage side of transformer when SPD is disconnected exceed the impulse withstand voltage 12kV, and the power frequency current at low-voltage side is 4.50-8.75 kA. Because switch-type SPD cannot cut off power frequency current, it is suggested that switch-type SPD should be replaced by zinc oxide arrester (YH10W-0.8/3.0) without follow current, whose lightning protection effect is verified by simulating calculation.

Key words: wind turbines, box-type transformer, ground potential rise, lightning overvoltage, power frequency current, surge protective device(SPD)