输电线路绝缘子、金具和导地线可靠度校准

冯云芬1,贡金鑫1,李宏男1,张子引2   

  1. 1.大连理工大学建设工程学部,辽宁省大连市 116024;2.国网北京经济技术研究院,北京市 102209
  • 出版日期:2014-05-01
  • 作者简介:冯云芬(1982),女,博士,主要从事工程结构可靠度与结构耐久性方面的研究工作,E-mail:fengyunfen@126.com; 贡金鑫(1964),男,博士,教授,博士生导师,主要从事工程结构可靠度、数值分析及钢筋混凝土结构耐久性方面的研究工作,E-mail:gong_jx.vip@eyou.com; 李宏男(1958),男,博士,长江学者特聘教授,博士生导师,主要从事大跨越输电塔体系的抗震计算理论、结构减震控制、重大工程健康监测与损伤评估等方面的研究工作,E-mail:hnli@dlut.edu.cn; 张子引(1971),男,本科,高级工程师,主要从事输电线路设计技术研究及电网工程评审和咨询工作,E-mail:zhangziyin@chinasperi.sgcc.com.cn。
  • 基金资助:

    国家自然科学基金委创新研究群体基金项目(51121005);国家电网公司科技项目(B3440912K006);高等学校学科创新引智计划资助项目(B08014)

Reliability Calibration of Insulator, Fitting and Ground Wre in Transmission Line

 

FENG Yunfen1, GONG Jinxin1, LI Hongnan1, ZHANG Ziyin2
  

  1. 1. Faculty of Infrastructure Engineering Dalian University of Technology, Dalian 116024, Liaoning Province, China;2.State Power Economic Research Institute, Beijing 102209, China
  • Online:2014-05-01

摘要:

为确定跨越高速铁路输电线路的可靠度水平,分析确定了绝缘子、金具和导地线的荷载、抗力的统计参数,采用考虑基本变量概率分布类型的一次二阶矩方法对按现行规范设计的输电线路的绝缘子、金具和导地线的可靠度进行了校准。分析表明,绝缘子串的可靠指标与绝缘子的联数及一联中绝缘子的数目有关。一联中绝缘子的数目按50考虑时,单联的平均可靠指标为3.45,双联为3.55。金具的平均可靠指标为3.55。对于导地线,永久荷载与风荷载组合时,弧垂最低点和悬挂点的平均可靠指标分别为4.90和4.45;永久荷载、风荷载与覆冰荷载组合时,弧垂最低点和悬挂点的平均可靠指标分别为4.55和4.15。与杆塔结构相比绝缘子、金具和导地线具有较高的可靠度水平。

关键词: 输电线路, 绝缘子, 金具, 导地线, 可靠度

Abstract:

To set the reliability level of transmission line crossing high speed railway, the statistical parameters of the load and resistance of insulators, fittings and ground wires were analyzed and determined. And the reliabilities of these members designed based on the current code were calibrate by using FOSM (first order second moment) method with considering the probability distribution type of basic variables. It is indicated that the reliability index of insulator string depends on the parallel number of strings and the number of insulator in one string. The reliability indexes of single and double insulator string with 50 insulators in one string are 3.45 and 3.55 respectively. The average reliability index of fittings is 3.55. The reliability index of ground wire at the sag’s lowest point or suspension point are 4.90 and 4.45respectively, in the combination of permanent load and wind load; and 4.45 and 4.15 respectively, in the combination of permanent load, wind load and ice load. The reliability indexes of insulators, fittings and ground wires are larger than that of transmission tower.

Key words: transmission line, insulator, fitting, ground wire, reliability, calibration