500 kV 输电线路舞动分析及治理

魏冲 潘少成 唐明贵 郭咏华 张祎 张金瑞

电力建设 ›› 2011, Vol. 32 ›› Issue (4) : 22-25.

PDF(1261 KB)
PDF(1261 KB)
电力建设 ›› 2011, Vol. 32 ›› Issue (4) : 22-25.
输配电技术

500 kV 输电线路舞动分析及治理

  • 魏冲1,潘少成1,唐明贵1,郭咏华1,张祎2,张金瑞1
作者信息 +

Analysis and Treatment of the Galloping of 500 kV Transmission Line

Author information +
文章历史 +

摘要

2009 年11 月至2010 年3 月初,受大风降温、雨雪冰冻等恶劣天气影响,河南电网发生了3 次大范围的输电线路覆冰舞动情况。其中500 kV输电线路舞动造成了线路跳闸和铁塔横担受损、螺栓脱落、跳线引流线破坏、绝缘子及间隔棒受损、防振锤滑移等故障,给河南电网正常运行造成了较大影响。统计了本次500 kV 线路舞动破坏的程度及特征,对舞动原因和电网受损情况原因进行深入分析,结合河南电网多年来的防舞治理经验,针对线路舞动受损的特点提出应对措施和建议。

Abstract

Large-scale conductor galloping of transmission lines occurred three times in Henan province from November 2009 to March 2010 caused by atrocious weather including gale, freezing rain and snow . Among them, the galloping of Henan 500 kV transmission lines caused such faults as line trip, tower cross arm damage, bolt desquamate, jumper drainage line damage, insulator and spacer damage and damper slip, which badly affected the normal operation of Henan power grid impact. The paper makes a statistical analysis of the galloping damages in terms of the extent and features and analyzes the galloping genesis and the causes of grid damages. Based on the anti-galloping experience of Henan power grid, some anti-galloping measures are proposed according to the galloping damage characteristics of transmission lines.

关键词

河南电网 / 输电线路 / 舞动 / 防舞设计 / 横担 / 跳线

引用本文

导出引用
魏冲 潘少成 唐明贵 郭咏华 张祎 张金瑞. 500 kV 输电线路舞动分析及治理[J]. 电力建设. 2011, 32(4): 22-25
Analysis and Treatment of the Galloping of 500 kV Transmission Line[J]. Electric Power Construction. 2011, 32(4): 22-25