1 000 kV变电构架风振系数的计算

陈寅 陈传新 郑威 张华

电力建设 ›› 2011, Vol. 32 ›› Issue (9) : 30-32.

PDF(491 KB)
PDF(491 KB)
电力建设 ›› 2011, Vol. 32 ›› Issue (9) : 30-32.
输配电技术

1 000 kV变电构架风振系数的计算

  • 陈寅1,陈传新2,郑威2,张华2
作者信息 +

Wind Vibration Coefficient Calculation of Trussed Frame in 1 000 kV Substation

Author information +
文章历史 +

摘要

基于准定常理论以及Davenport谱计算1 000 kV三跨变电构架风振系数,并与按照规范方法计算得到的风振系数进行比较。计算结果表明:1 000 kV三跨变电构架风振系数较单塔有不同程度的增大;根据规范所得风振系数总体来说对于边塔偏于保守,而对于中塔偏于危险。计算结果在工程设计中需要引起注意。

Abstract

Base on quasi-steady theory and Davenport spectrum, wind vibration coefficients of 1 000 kV three-span trussed frame are calculated, which is compared with that calculated by the standard method. It is shown that the wind vibration coefficient of 1 000 kV three-span trussed frame are higher than that of single tower, which calculated by standard method are conservative for edge tower and dangerous for middle tower. The results obtained in the paper need to be given attention to in engineering design.

关键词

准定常理论 / Davenport谱 / 1 000 kV变电构架 / 风振系数

Key words

quasi-steady assumptions;Davenport spectrum;trussed frame of 1 000    / kV substation / wind vibration coefficient

引用本文

导出引用
陈寅 陈传新 郑威 张华. 1 000 kV变电构架风振系数的计算[J]. 电力建设. 2011, 32(9): 30-32
Wind Vibration Coefficient Calculation of Trussed Frame in 1 000 kV Substation[J]. Electric Power Construction. 2011, 32(9): 30-32
中图分类号: TM753   

PDF(491 KB)

Accesses

Citation

Detail

段落导航
相关文章
AI小编
你好!我是《电力建设》AI小编,有什么可以帮您的吗?

/