西北电网主变充电引起青藏直流闭锁的原因分析及对策

种芝艺,粟小华,刘宝宏

电力建设 ›› 2013, Vol. 34 ›› Issue (3) : 88-91.

PDF(490 KB)
PDF(490 KB)
电力建设 ›› 2013, Vol. 34 ›› Issue (3) : 88-91.
运行与管理

西北电网主变充电引起青藏直流闭锁的原因分析及对策

  • 种芝艺1,粟小华2,刘宝宏1
作者信息 +

Analysis and Countermeasures of Qinghai-Tibet DC Blocking Caused by   Main Transformer Charging in Northwest Power Grid

  • CHONG Zhiyi1,SU Xiaohua2,LIU Baohong1
Author information +
文章历史 +

摘要

根据系统谐波阻抗扫描和EMTDC仿真验证,分析了西北电网主变充电产生的2次谐波电压在柴达木换流站放大的原因,提出了抑制变压器合闸励磁涌流的措施。为了降低西北电网主变充电产生的2次谐波对直流系统运行的影响,利用直流系统设备耐受谐波的能力,在交流系统安全稳定的条件下对直流谐波保护进行了优化,并应用到青藏工程中。优化后的谐波保护提高了青藏直流联网工程适应弱交流系统的能力,降低了直流系统强迫停运的概率。

Abstract

Through harmonic impedance scanning and EMTDC simulation of AC system, the reason why the second-harmonic voltage, generated by the main transformers charging in the northwest power grid, was amplified in Chaidamu converter station is analyzed in this paper. Then some countermeasures are put forward to inhibit the inrush current during transformer switching-in. In order to reduce the impact of secondharmonic on the operation of DC system, based on the equipments’ harmonic tolerance capacity in DC system, the DC harmonic protection under the security and stability condition of AC system is optimized, which has been applied to the Qinghai-Tibet Project. The optimized harmonic protection can improve the adaptability of Qinghai-Tibet DC Project to the weak AC system, and reduce the forced outage rate of DC system.

关键词

弱交流系统 / 直流输电 / 励磁涌流 / 谐波保护

Key words

weak AC system / DC power transmission / inrush current / harmonic protection

引用本文

导出引用
种芝艺,粟小华,刘宝宏. 西北电网主变充电引起青藏直流闭锁的原因分析及对策[J]. 电力建设. 2013, 34(3): 88-91
CHONG Zhiyi,SU Xiaohua,LIU Baohong. Analysis and Countermeasures of Qinghai-Tibet DC Blocking Caused by   Main Transformer Charging in Northwest Power Grid[J]. Electric Power Construction. 2013, 34(3): 88-91

参考文献

[1]徐政.联于弱交流系统的直流输电特性研究之一:直流输电的输送能力[J].电网技术,1997,21(1):12-16.



[2]徐政.联于弱交流系统的直流输电特性研究之二:控制方式与电压稳定性[J].电网技术,1997,21(3):1-4.



[3]Nayak O B,Gole A M,Chapman D G,et al.Dynamic performance of smile and synchronous compensators at an HVDC inverter bus in a very weak AC system[J].IEEE Trans on Power Delivery,1994,9(3):1350-1358.



[4]Zhuang Y,Menzies R W, Nayak O B,et al.Dynamic performance of a STATCOM at an HVDC inverter feeding a very weak AC system[J].IEEE Trans on Power Delivery,1996,11(2):958-964.



[5]周长春,徐政.联于弱交流系统的HVDC故障恢复特性仿真分析[J].电网技术,2003,27(11):18-21.



[6]罗德彬,汪峰,徐叶玲.国家电网公司直流输电系统典型故障分析[J].电网技术,2006,30(1):35-39.



[7]Franken B.Analysis of HVDC converters connected to weak Ac systems[J].IEEE Transaction on Power System,1990,5 (1):235-242.



[8]CIGRE WG 14.07,IEEE WG 15.05.Guide for planning DC links terminating at AC system locations having low short circuit capacities[J].Electra,1992,142(1):119-123.



[9]宗洪良,金华峰,朱振飞,等.基于励磁阻抗变化的变压器励磁涌流判别方法[J].中国电机工程学报,2001,21(7):91-94.



[10]葛宝明,王祥珩,苏鹏声,等.电力变压器励磁涌流判据及其发展方向[J].电力系统自动化,2003,27(22):1-5.



[11]马玉龙,蒲莹,卢亚军,等.青藏直流联网工程控制保护系统联调报告[R].北京:国家电网公司直流建设分公司,2011.



[12]赵畹君.高压直流输电工程技术[M].北京:中国电力出版社,2004:106-112.



[13]浙江大学直流输电科研组.直流输电[M].北京:水利水电出版社,1985:258-259.



[14]张雪松,何奔腾.变压器励磁涌流的相移比较鉴别方法[J].中国电机工程学报,2005,25(19):43-47.



[15]焦邵华,刘万顺.区分变压器励磁涌流和内部短路的积分型波形对称原理[J].中国电机工程学报,1999,19(8):35-38.



[16]孙洋,刘翔,黄家栋.应用等效瞬时电感对称特征判别变压器励磁涌流新方法[J].中国电力,2010,43(11):26-30.



[17]王国兴,张传利.变压器励磁涌流判别方法的现状及发展[J].中国电力,1998,31(10):19-22.