空冷风机单元振动故障原因分析及处理
Analysis and Treatment for Vibration Fault of Air-cooling Fan
针对山西右玉电厂330 MW直接空冷机组空冷风机单元振动问题,对风机单元进行了测试和分析,给出了风机、减速机及风机桥架的振动规律。通过采取风机桥架加固、将风机由5叶改为6叶等措施,消除了空冷风机单元振动故障。此次振动故障的处理过程及相关试验结果,对风机单元设计及施工具有一定的借鉴意义。
Aimed to the vibration fault of air-cooling fan in 330 MW direct air-cooling units in Shanxi Youyu Power Plant, the vibration rule of fan, reducer and fan bridge is gained through a series of analyses and tests on fan. The vibration fault of air-cooling fan could be eliminated by some measures, such as the reinforcement of fan bridge, and changing the fan blade number from 5 to 6. These vibration fault treatments and test results could provide references for fan’s design and construction.
空冷风机 / 风机桥架 / 减速机 / 电机 / 振动 / 自振频率 / 叶片数量
air-cooling fan / fan bridge / reducer / motor / vibration / natural frequency / blade number
[1]王勇强,雷平和,张凌伟,等.某电厂直接空冷风机单元振动分析[J].电力建设,2012,33 (7):50-52.
中国电力工程顾问集团华北电力设计院工程有限公司科研项目(Y2010-A19);京能集团2011—2012年度科研项目(直接空冷风机单元振动问题研究)。