500 kV隔离开关控制接触器频繁故障的原因分析及反事故措施

邓光武 宋述波 王超 林庆标 莫文斌

电力建设 ›› 2012, Vol. 33 ›› Issue (2) : 88-91.

PDF(591 KB)
PDF(591 KB)
电力建设 ›› 2012, Vol. 33 ›› Issue (2) : 88-91.
运行与管理

500 kV隔离开关控制接触器频繁故障的原因分析及反事故措施

  • 邓光武1,宋述波1,2,王超1,林庆标1,莫文斌1
作者信息 +

Cause Analysis of Frequent Breakdown and Anti-accident Measures for Control Contactor in 500 kV Disconnecter

Author information +
文章历史 +

摘要

通过分析500 kV隔离开关控制接触器在操作过程中的电压、电流波形,认为在接触器线圈励磁返回瞬间,线圈回路出现的暂态冲击是造成其频繁故障的原因,提出了在接触器线圈两端加装消弧回路的反事故措施。通过对2种消弧回路的效果对比,最终选择加装二极管串联电阻的消弧回路。

Abstract

Frequent breakdown occurs for control contactor in 500 kV disconnecter, due to the transient arc surge appearing in the coil circuit at the moment of excitation return, by analyzing the voltage and current waveforms during the operation of control contactor. Therefore, the anti-accident measures are proposed by applying the arc suppression circuit to the control contactor coil. By comparing the effect of two kinds of arc suppression circuit, an arc suppression circuit with the diode and series resistance is selected.

引用本文

导出引用
邓光武 宋述波 王超 林庆标 莫文斌. 500 kV隔离开关控制接触器频繁故障的原因分析及反事故措施[J]. 电力建设. 2012, 33(2): 88-91
Cause Analysis of Frequent Breakdown and Anti-accident Measures for Control Contactor in 500 kV Disconnecter[J]. Electric Power Construction. 2012, 33(2): 88-91