ELECTRIC POWER CONSTRUCTION ›› 2013, Vol. 34 ›› Issue (10): 107-111.doi: 10.3969/j.issn.1000-7229.2013.10.021

Previous Articles     Next Articles

Analysis of Converter Valve Control VBE-RDY Null Value Fault in Jinsu UHVDC Project

YANG Wankai1,ZENG Nanchao1,LIU Fei2   

  1. 1.    China Electric Power Research Institute, Beijing 100192, China, 2. Xi’an XD Power System Co., Ltd., Xi’an 710075, China
  • Online:2013-10-01

Abstract:

 

The converter valve control and monitoring functions based on SIEMENS technology were analyzed for Jinsu (from Jinping to Suzhou) 800 kV UHVDC power transmission project. The signals between Valve Base Electronics (VBE) and Converter Control and Protection (CCP) were analyzed too. The reasons of VBE READY (VBE-RDY) null value and making VBE out of operation were researched while DC bus differential protection tripping of Jinping converter station simulated pole 2 high voltage converter during Jinsu 800 kV UHVDC system commissioning tests. Moreover, the principle of converter valve bypass and VBE-RDY null value were analyzed in detail. The VBE trip and converter block fault caused by VBE cabinet 110 V DC power loss test was analyzed and researched in pole 1 low voltage converter system commissioning tests. The solutions to solve above problems were proposed and will be put into practice in the following 800 kV UHVDC transmission project.

Key words: Jinsu UHVDC power transmission project, converter valve control, VBE bypass, VBE-RDY null value fault