• CSCD核心库收录期刊
  • 中文核心期刊
  • 中国科技核心期刊

ELECTRIC POWER CONSTRUCTION ›› 2013, Vol. 34 ›› Issue (11): 51-55.doi: 10.3969/j.issn.1000-7229.2013.11.010

Previous Articles     Next Articles

Overvoltage and Insulation Coordination of DC Filter in ±1 100 kV UHVDC Power Transmission Project

XIE Longjun1,WANG Bangtian2,FAN Shaojie3,HUANG Yekuang2,LI Li1,LI Hua1   

  1. 1. College of Electrical and Electronic Engineering, Huazhong University of Science and Technology, Wuhan 430074, China; 2.XJ Group Corporation, Xuchang 461000, Henan Province, China; 3.27th Institute, China Electronics Technology Group Corporation, Zhengzhou 450047, China
  • Online:2013-11-01

Abstract:

DC filter is one of the critical devices in HVDC power transmission project. The configuration scheme and parameter selection process of arrester in DC filter were analyzed in-depth, and the specific expression of arrester parameters was presented. Two typical fault conditions which played decisive roles on the insulation level of DC filter were studied: ground fault on DC line and incoming switching surge on DC line; meanwhile the calculation model of these fault conditions were introduced, in which fault inductance between fault point and high-voltage side of DC filter should be considered. Based on the practical ±1 100 kV UHVDC transmission project, the overvoltage of DC filter devices was also calculated. The maximum transient overvoltage of all the DC-filter devices was presented in the calculation result, and then the final insulation level of DC-filter devices in this UHVDC project was determined according to their insulation margin, which could provide the basis for the selection of equipment and manufacturing.

Key words: ±1 100 kV UHV, UHVDC, DC filter, overvoltage, arrester, insulation level