• CSCD核心库收录期刊
  • 中文核心期刊
  • 中国科技核心期刊

ELECTRIC POWER CONSTRUCTION ›› 2015, Vol. 36 ›› Issue (3): 1-6.doi: 10.3969/j.issn.1000-7229.2015.03.001

    Next Articles

Steady-State Operating Range of MMC-HVDC

ZHANG Jing1,SUN Weizhen1,FEI Jianping2,LIU Mingkang2,ZHANG Zheren3,XU Zheng3   

  1. 1. Zhejiang Electric Power Company, Hangzhou 310007, China; 2. Zhoushan Electric Power Company, Zhoushan 316021, Zhejiang Province, China; 3. Department of Electric Engineering, Zhejiang University, Hangzhou 310027, China
  • Online:2015-03-01

Abstract:

This paper studied the influence of AC system on the operating range of MMC-HVDC (modular multilevel converter-high voltage direct current) under steady-state condition, and analyzed the key factors to limit the DC power transmission capacity. Firstly, the equivalent mathematical model of a one-terminal MMC-HVDC was derived. Secondly, the impacts of the short circuit ratio (SCR) of AC system, the capacities of converter transformer and converter station on the steady-state operating range of converter station were studied. Lastly, this paper analyzed the influence of the parallel reactive power compensator on the operating range of MMC-HVDC. The calculation results show that: the operating range of MMC-HVDC is mostly limited by the converter transformer capacity under large SCR of AC system; while the operating range is largely depended on the value of SCR under small SCR. Additionally, the use of reactive power compensator can improve the operating range of MMC-HVDC.

Key words: modular multilevel converter (MMC), VSC-HVDC, steady-state operating range, short circuit ratio , of AC system, reactive power compensator, converter transformer capacity