• CSCD核心库收录期刊
  • 中文核心期刊
  • 中国科技核心期刊

ELECTRIC POWER CONSTRUCTION ›› 2015, Vol. 36 ›› Issue (3): 65-70.doi: 10.3969/j.issn.1000-7229.2015.03.011

Previous Articles     Next Articles

Adaptive Undervoltage Load Shedding Strategy Based on Disturbance Scale Discrimination of Transient Voltage

LIU Wei1, LI Ye2, ZHANG Baohui2, LEI Junzhe1   

  1. 1. State Grid Henan Electric Power Research, Zhengzhou 450052, China; 2. School of Electrical Engineering, Xi’an Jiaotong
    University, Xi’an 710049, China
  • Online:2015-03-01

Abstract:

Conventional  undervoltage load shedding(UVLS) scheme only focuses on local voltages without considering the response characteristics of transient voltage in whole gird. This paper analyzed the relationship between transient voltage drops and disturbance scale, proposed discriminant index for the disturbance scale of transient voltages based on the offset of voltage drops, and divided the transient voltage disturbance into two categories: the whole-grid transient voltage disturbance and the partial-region transient voltage disturbance. On the basis of the discriminant index results, an adaptive UVLS strategy based on the disturbance scale discrimination of transient voltages was constructed, with consideration on the dynamic process of voltage and frequency after the disturbance, which could solve the whole-grid transient voltage disturbance and the partial-grid transient voltage disturbance respectively with two adaptive load shedding schemes. Finally, the effectiveness and superiority of this strategy in different instability scenarios were verified by the simulation on the IEEE 39-bus system.

Key words: voltage stability, disturbance scale, load shedding, dynamic frequency, adaptive control