Adaptive Undervoltage Load Shedding Strategy Based on Disturbance Scale Discrimination of Transient Voltage

LIU Wei, LI Ye, ZHANG Baohui, LEI Junzhe

Electric Power Construction ›› 2015, Vol. 36 ›› Issue (3) : 65-70.

PDF(519 KB)
PDF(519 KB)
Electric Power Construction ›› 2015, Vol. 36 ›› Issue (3) : 65-70. DOI: 10.3969/j.issn.1000-7229.2015.03.011

Adaptive Undervoltage Load Shedding Strategy Based on Disturbance Scale Discrimination of Transient Voltage

  • LIU Wei1, LI Ye2, ZHANG Baohui2, LEI Junzhe1
Author information +
History +

Abstract

Conventional  undervoltage load shedding(UVLS) scheme only focuses on local voltages without considering the response characteristics of transient voltage in whole gird. This paper analyzed the relationship between transient voltage drops and disturbance scale, proposed discriminant index for the disturbance scale of transient voltages based on the offset of voltage drops, and divided the transient voltage disturbance into two categories: the whole-grid transient voltage disturbance and the partial-region transient voltage disturbance. On the basis of the discriminant index results, an adaptive UVLS strategy based on the disturbance scale discrimination of transient voltages was constructed, with consideration on the dynamic process of voltage and frequency after the disturbance, which could solve the whole-grid transient voltage disturbance and the partial-grid transient voltage disturbance respectively with two adaptive load shedding schemes. Finally, the effectiveness and superiority of this strategy in different instability scenarios were verified by the simulation on the IEEE 39-bus system.

Key words

voltage stability / disturbance scale / load shedding / dynamic frequency / adaptive control

Cite this article

Download Citations
LIU Wei, LI Ye, ZHANG Baohui, LEI Junzhe. Adaptive Undervoltage Load Shedding Strategy Based on Disturbance Scale Discrimination of Transient Voltage[J]. Electric Power Construction. 2015, 36(3): 65-70 https://doi.org/10.3969/j.issn.1000-7229.2015.03.011

References

[1]孙华东,汤涌,马世英.电力系统稳定的定义与分类评述[J].电网技术,2006,30(17):31-35.
Sun Huadong,Tang Yong,Ma Shiying.A commentary on definition and classification of power system stability[J].Power System
Technology,2006,30(17):31-35.
[2]薛禹胜.时空协调的大停电防御框架:(三)各道防线内部的优化和不同防线之间的协调[J].电力系统自动化,2006,30(3):1-
10,106.
Xue Yusheng. Space-time cooperative framework for defending blackouts: Part Ⅲ optimization and coordination of defense-lines
[J]. Automation of Electric Power Systems, 2006, 30(3): 1-10,106.
[3]Sigrist L,Egido I,Rouco L.Frequency stability boundary of small isolated power systems[J].Electric and Electronics
Engineers,2010:229-233.
[4]马世英,易俊,孙华东,等.电力系统低压减载配置原则及方案[J].电力系统自动化,2009,33(5):45-49.
Ma Shiying,Yi Jun,Sun Huadong, et al. Study on configuration of under-voltage load shedding in power systems[J].Automation
of Electric Power Systems,2009,33(5):45-49.
[5]邢国华,乔卫东.低压减载方案研究综述[J].华东电力,2005,33(12):23-26.
Xing Guohua, Qiao Weidong. Study of undervoltage load shedding schemes[J]. East China Electric Power,2005,33(12):23-26.
[6]薛禹胜,任先成,WU Q H,等.关于低频低压切负荷决策优化协调的的评述[J].电力系统自动化,2009,33(9):100-107.
Xue Yusheng,Ren Xiancheng,WU Q H,et al.A review on optimization and coordination of under frequency/voltage load shedding
[J].Automation of Electric Power Systems, 2009,33(9):100-107.
[7]陈树勇,朱琳,丁剑,等.风电场并网对孤网高频切机的影响研究[J].电网技术,2012,36(1):58-64.
Chen Shuyong, Zhu Lin, Ding Jian, et al. Impact of grid-connected wind farms on high frequency generator tripping in isolated
power grid[J]. Power System Technology,2012,36(1):58-64.
[8]王一振,马世英,王青,等.电力系统孤网高频问题研究现状和发展趋势[J].电网技术,2012,36(12):165-169.
Wang Yizhen, Ma Shiying, Wang Qing, et al. Present status and developing trend of research on over frequency in isolated
power grid[J].Power System Technology,2012,36(12):165-169.
[9]Novosel D,Madani V,Bhargava B,et al.Dawn of the grid synchronization:Benefits,practical applications,and
deployment strategies for wide area monitoring,protection,and control[J].IEEE Power Energy Magazine,2008,6(1):49-60.
[10]Cai J Y,Huang Zhenyu,Hauer J,et al.Current status and experience of WAMS implementation in North America
[C]//Transmission and Distribution Conference and Exhibition,2005:1-7.
[11]Xie Xiaorong,Xin Yaozhong,Xiao Jinyu,et al.WAMS applications in Chinese power systems[J].IEEE Power Energy
Magazine,2006,6(1):54-63.
[12]De La Ree Jaime,Centeno V,Thorp J S,et al.Synchronized. Phasor measurement applications in power systems[J].IEEE
Transactions on Smart Grid,2010,1(1):20-27.
[13]Glavic M,Van Cutsem T.Wide-area detection of voltage instability from synchronized phasor measurements[J].IEEE
Transactions on Power Systems,2009,24(3):1408-1416.
[14]Prasetijo D,Lachs W R,Sutanto D.A new load shedding scheme for limiting underfrequency[J].IEEE Transactions on
Power Systems,1994,9(3):1371-1378.
[15]Seethalekshmi K,Singh S N,Srivastava S C.WAMS assisted frequency and voltage stability based adaptive load shedding[
J].IEEE Power and Energy Society General Meeting.IEEE,2009:1-8.
[16]Tang Junjie,Liu Junqi,Ferdinanda Ponci,et al.Adaptive load shedding based on combined frequency and voltage
stability assessment using synchrophasor measurements[J].IEEE Transactions on Power Systems,2013,28(2):2035-2047.
[17]Aboul-Seoud T,Jatskevich J.Dynamic modeling of induction motor loads for transient voltage stability studies
[C]//Electric Power Conference.Canada:IEEE,2008:1-5.
PDF(519 KB)

Accesses

Citation

Detail

Sections
Recommended

/