• CSCD核心库收录期刊
  • 中文核心期刊
  • 中国科技核心期刊

Electric Power Construction ›› 2017, Vol. 38 ›› Issue (8): 2-.doi: 10.3969/j.issn.1000-7229.2017.08.001

Previous Articles     Next Articles

Current-Breaking Test Method Based on LC Source for Hybrid HVDC Circuit Breaker

DING Xiao1, TANG Guangfu2,HAN Minxiao1,GAO Chong2, WANG Gaoyong2#br#   

  1. (1. School of Electric and Electronic Engineering, North China Electric Power University, Beijing 102206, China;2. Global Energy Interconnection Research Institute, Beijing 102209, China)
  • Online:2017-08-01
  • Supported by:
     

Abstract: ABSTRACT:  Current-breaking test is the core part of the operation tests for DC circuit breaker, whose effectiveness is directly related to the verification of the electrical performance of DC circuit breakers. This paper studies the current-breaking test method of hybrid HVDC circuit breaker for MMC-HVDC system, aiming to present the current-breaking test method and  test parameters for engineering feasibility. Firstly, based on the analysis of the principle and working condition of hybrid  HVDC circuit breaker, we reveal the its stress characteristics; then, on the basis of stress extraction, we present the LC source test circuit and parameters; finally, we verify the accuracy of the simulation circuit and test method through the short-circuit current-breaking test for a 200 kV circuit breaker, whose results can provide reference for the current-breaking test design of hybrid HVDC circuit breaker.

Key words:  MMC-HVDC, LC circuit, hybrid HVDC circuit breaker, operation test, breaking test, stress analysis

CLC Number: