Simulation Study on Electromagnetic Influence of 750 kV Double Circuit Transmission Lines in Xinjiang on Nearby Petroleum & Gas Pipelines

DONG Tiezhu 1,BAI Feng2,LI Haipeng3,WU Haiyang1, YANG Wenhui1,LI Xiangmin1,WANG Hongxuan1   

  1. 1.Qinghai Provincial Electric Power Design Institute, Xining 810008, China; 2.China Electric Power Research Institute, Beijing 100192, China;3.Xining Power Supply Company, Xining 810008, China
  • Online:2013-08-01

Abstract: In order to study the electromagnetic influence of 750 kV double-circuit (consisting of two parallel single circuit) AC transmission lines in China on nearby petroleum & gas pipelines, the electromagnetic environment of the petroleum & gas pipeline nearby a 750 kV AC transmission line was simulated by using a software of CDEGS. Based on the domestic and international standards, the limits of the electromagnetic influences of AC transmission lines on nearby petroleum & gas pipelines were proposed, and the interference voltage of the pipelines were calculated and analyzed under different operating conditions of AC transmission lines. Through the comparison of the simulation results and the limits, analysis and assessment were performed on the degree of electromagnetic influences of 750 kV double-circuit AC transmission lines on petroleum & gas pipelines, and some protective measures were suggested.

Key words: 750 kV double-circuit, AC power transmission line, petroleum & gas pipeline, electromagnetic influence, single-phase short circuit, protective measures