• CSCD核心库收录期刊
  • 中文核心期刊
  • 中国科技核心期刊

ELECTRIC POWER CONSTRUCTION ›› 2014, Vol. 35 ›› Issue (1): 88-92.doi: 10.3969/j.issn.1000-7229.2014.01.017

Previous Articles     Next Articles

Influences of Windshield around Air-Cooled Island on Condenser Heat Transfer Efficiency

ZHOU Lanxin, WANG Xiaofei, WU Ruikang   

  1. Key Laboratory of Ministry of Condition Monitoring and Control for Power Plant Equipment (North China Electric Power University), Baoding 071003, Hebei Province, China
  • Online:2014-01-01

Abstract:

Taking a 600 MW direct air-cooling unit as an example, the influence of environmental wind on the heat transfer efficiency of air-cooled condenser was numerically simulated by using CFD software (Fluent), and the schemes of different windshields installed around the air cooling platform were put forward. The calculation results show that the installation of windshield can reduce the influence of hot air recirculation and the ‘intrusion’ phenomenon, as well increase the air flow in air cooling unit and the average heat transfer of condenser, which can be up to 72.52% and 24.51% higher than that without windshield, under 0 m/s-12 m/s environmental wind speed.

Key words: direct air-cooling unit, condenser, windshield, numerical simulation, heat transfer efficiency