• CSCD核心库收录期刊
  • 中文核心期刊
  • 中国科技核心期刊

ELECTRIC POWER CONSTRUCTION ›› 2014, Vol. 35 ›› Issue (3): 13-17.doi: 10.3969/j.issn.1000-7229.2014.03.003

Previous Articles     Next Articles

Lighting Intruding Wave Overvoltage of Three-Terminal Flexible DC Transmission System

LI Tianwei1, LIU Dapeng2, LEI Yuanyuan1, ZHAO Yuming1, XIANG Yang1, LI Xiaolin1   

  1. 1. Electric Power Research Institute, CSG, Guangzhou 510080, China; 2. Xi’an XD Power Systems Co., Ltd., Xi’an 710077, China
  • Online:2014-03-01

Abstract:

The overvoltage of lightning intruding wave is the important basis for determining equipment insulation level in DC transmission system converter station. This paper built the simulation calculation model of lightning intruding wave for ±160 kV Nan’ao three-terminal flexible DC transmission system at DC side, with using PSCAD/EMTDC software. Then, the maximum shielding failure current of DC transmission line was calculated by electrical geometry model (EGM) and the intersection method was used as the criterion for air gap flashover. Finally, the voltage stresses of pole bus equipment and connection cable were calculated for the convertor station after DC transmission line suffering from the lightning shielding failure and counterattack, and the equipment’s insulation level for lightning impulse was checked. The results show that the insulation margin of the equipment meets the requirements.

Key words: flexible DC transmission, lightning intruding wave, overvoltage, electrical geometry model