PDF(468 KB)
Research on Tower Grounding Resistance Measurement in Northwest Region with High Soil Resistivity
Electric Power Construction ›› 2011, Vol. 32 ›› Issue (9) : 33-36.
PDF(468 KB)
PDF(468 KB)
Research on Tower Grounding Resistance Measurement in Northwest Region with High Soil Resistivity
The grounding resistance measurement instrument fails in high soil resistivity because the grounding resistance is too high of auxiliary grounding detection rod from the theoretical analysis. In order to improve the sensitivity of measurement instrument, it is proposed to increase the length and diameter of auxiliary grounding detection rod, enhance the water content of soil and apply salt for decreasing resistance. The correctness and reasonability of the proposed method are validated by field experiment.
high soil resistivity / grounding resistance / measurement / ZC-8 / grounding modes / auxiliary grounding detection rod
/
| 〈 |
|
〉 |