Back-pressure Fuzzy Control of Direct Air Cooled Unit

Electric Power Construction ›› 2012, Vol. 33 ›› Issue (1) : 6-11.

PDF(705 KB)
PDF(705 KB)
Electric Power Construction ›› 2012, Vol. 33 ›› Issue (1) : 6-11.

Back-pressure Fuzzy Control of Direct Air Cooled Unit

Author information +
History +

Abstract

Air-cooling systems and water-cooling systems of steam turbine differ much in their ends of exhaust, as a result that the method of back pressure control for ordinary water-cooling systems is not applicable to air-cooling systems. Therefore, the safety margin of back-pressure control is provided, based on which the fuzzy control approach is proposed for applying in direct air-cooled units. The back pressure of air cooled steam condenser is easy to be influenced by the local environmental temperature and the fans speed, so that a mathematical model is developed based on the traditional air-cooled units with off-design characteristics. It is verified by the simulation that the approach to a large extent can ensure the air-cooling system operating under most cost-efficient and safest conditions.

Key words

/ font-size: 10.5pt / mso-bidi-font-size: 12.0pt / mso-font-kerning: 1.0pt / mso-ansi-language: EN-US / mso-fareast-language: ZH-CN / mso-bidi-language: AR-SA / mso-fareast-font-family: 宋体" lang="EN-US">direct air cooled unit / back pressure / safety margin / fuzzy control

Cite this article