Back-pressure Fuzzy Control of Direct Air Cooled Unit

  

  • Received:2011-09-20 Revised:2011-11-07 Online:2012-01-01 Published:2012-05-31
  • Contact: Yu-Feng GUO E-mail:gyufeng_hit@163.com

Abstract:

Air-cooling systems and water-cooling systems of steam turbine differ much in their ends of exhaust, as a result that the method of back pressure control for ordinary water-cooling systems is not applicable to air-cooling systems. Therefore, the safety margin of back-pressure control is provided, based on which the fuzzy control approach is proposed for applying in direct air-cooled units. The back pressure of air cooled steam condenser is easy to be influenced by the local environmental temperature and the fans speed, so that a mathematical model is developed based on the traditional air-cooled units with off-design characteristics. It is verified by the simulation that the approach to a large extent can ensure the air-cooling system operating under most cost-efficient and safest conditions.

Key words: font-size: 10.5pt, mso-bidi-font-size: 12.0pt, mso-font-kerning: 1.0pt, mso-ansi-language: EN-US, mso-fareast-language: ZH-CN, mso-bidi-language: AR-SA, mso-fareast-font-family: 宋体" lang="EN-US">direct air cooled unit, back pressure, safety margin, fuzzy control