Abstract

The ultimate bearing capacity of transmission towers with steel tube and angle steel combined is analyzed by the finite element software of ANSYS in the conditions of ground motion. The ultimate bearing capacity calculated by displacement loading method shows that one support of transmission tower sinks deeply. In order to improve torsion resistance of the tower, both the steel bars near the supports and transverse bars near the changing slope should be strengthened, and some foundation treatment schemes are proposed in this paper.

Cite this article

Download Citations
Calculation of Ultimate Bearing Capacity and Foundation Treatment of Transmission Tower in Ground Motion[J]. Electric Power Construction. 2012, 33(2): 40-43