PDF(3742 KB)
Crack Analysis of T23 Steel Tube Welded Joints for 1 000 MW Ultra Supercritical Tower-type Boiler
Electric Power Construction ›› 2012, Vol. 33 ›› Issue (4) : 90-92.
PDF(3742 KB)
PDF(3742 KB)
Crack Analysis of T23 Steel Tube Welded Joints for 1 000 MW Ultra Supercritical Tower-type Boiler
The macro-inspection and microstructure analysis of cracks for welded joints were investigated, according to the leakage of T23 Steel tube welded joints in a 1 000 MW ultra supercritical tower-type boiler. The result shows that the water-wall tube weld cracks are caused by residual stress and structural binding stress of welded joints.
/
| 〈 |
|
〉 |