Electric Power Construction ›› 2012, Vol. 33 ›› Issue (7) : 21-25.

PDF(978 KB)
PDF(978 KB)
Electric Power Construction ›› 2012, Vol. 33 ›› Issue (7) : 21-25.

Analysis on Electric Unbalance Degree for 1 000 kV Mixed Transmission Line with Single-circuit and Double-circuit on Same Tower

Author information +
History +

Abstract

For the Ximeng-Beijing east section of 1 000 kV Ximeng-Nanjing ultra high voltage transmission line, this paper calculated the electric unbalance degree and best transposition position of the mixed transmission line with single-circuit and double-circuit on same tower based on ATP-EMTP. The results shows that the best transposition point is not the 1/3 or 2/3 equal position of lines. Basing on electric unbalance degree, this paper recommends that the lines has a full transposition in single-circuit sections without transposition in double-circuit sections with negative phase sequence, and two transposition towers are located at 63.14 and 103.13 km.

Cite this article

Download Citations
Analysis on Electric Unbalance Degree for 1 000 kV Mixed Transmission Line with Single-circuit and Double-circuit on Same Tower[J]. Electric Power Construction. 2012, 33(7): 21-25