Simulation Study of Influence of HVDC Power Transmission Lines on Railway Communication Lines

  • LV Sizhuo,WEN Jun,LIU Lianguang,CAO Wenjia,ZHOU Siyu
Author information +
History +

Abstract

A variety of signal cables are used in railway communication system to connect signal equipments, while HVDC power transmission lines in fault condition and DC side harmonics exert impact on railway communication lines. So the research on the influence degree of railway communication has practical significance to ensure railway transport efficiency. According to the principle of electromagnetic induction of power lines on weak current circuit, the theory and calculation methods of influence of HVDC power transmission lines on railway communication lines are introduced in this paper. Based on the limit of influence of HVDC transmission lines on communication lines in China, the induced voltage and disturbance voltage are calculated and simulated in PSCAD/EMTDC with the changes of different parameters, in which the influence degree of different parameters on induced voltage and disturbance voltage is obtained. Finally, some protective measures are suggested to restrain dangerous effects and interference effects.

Key words

HVDC / railway telecommunication / dangerous effects / interference effects / induced voltage

Cite this article

Download Citations
LV Sizhuo,WEN Jun,LIU Lianguang,CAO Wenjia,ZHOU Siyu. Simulation Study of Influence of HVDC Power Transmission Lines on Railway Communication Lines[J]. Electric Power Construction. 2013, 34(4): 37-42

References

[1]王国雨.电气化铁路通信系统设计应注意的几个问题[J].铁道勘测与设计,2007(1):8-11.

[2]姜贺彬.牵引供电系统对铁路信号系统的电磁干扰分析[D].成都:西南交通大学,2009.

[3]王建国,刘洋,孙建明.铁路10  kV三相电力电缆接地短路电流对通信信号电缆的电磁影响[J].中国铁道科学,2008,29(4) :109-

115.

[4]常媛媛,张晨.高速铁路信号电缆不同接地方式对芯线的干扰影响研究[J].中国铁路,2010(4):27-33.

[5]陆家榆,鞠勇,庞廷智.±800  kV直流输电线路对电信线路的危险和干扰影响研究[J].中国电力,2007,40(4):20-25.

[6]赵世雄. 云广±800  kV直流输电线路电磁感应的等效短路电流探讨[J].南方电网技术,2010,4(4):37-39.

[7]熊万洲.±800  kV直流输电等效干扰电流指标分析[J].电网技术,2008,32(2):81-85.

[8]于文志,强玉平.直流输电线路对电信线路危险影响的计算方法[J].电网与水力发电进展,2007,23(12):20-25.

[9]熊万洲. 直流输电线路故障对电信线路感应的计算[J].电力建设,2005,26(8):32-36.

[10]赵畹君. 高压直流输电工程技术[M].北京:中国电力出版社,2004.

[11]DL/T 5340—2006 直流输电线路对电信线路危险影响防护设计技术规定[S].

[12]周皓静,刘红杰.现代标准对通信音频干扰限值的规定[J].电信工程技术与标准化,2007,20(10):44-48.

[13]熊万洲. 行业标准DL/T5340在高压直流输电工程设计中的应用[C]//无线电干扰和变电站电磁兼容研讨会论文集,2008.

[14]DL/T 5033—2006 送电线路对电信线路危险和干扰影响防护设计规程[S].

[15]TB 10006—99 铁路通信设计规范[S].
PDF(714 KB)

Accesses

Citation

Detail

Sections
Recommended

/