Research on Embedded Monitoring System for Transformer's Partial Discharge
LI,LI Junqing,ZHANG Jianghui,WANG Baochen
Electric Power Construction ›› 2013, Vol. 34 ›› Issue (6) : 82-86.
PDF(549 KB)
PDF(549 KB)
Research on Embedded Monitoring System for Transformer's Partial Discharge
An embedded monitoring system that was used to acquire partial discharge (PD) ultrasonic in transformer was designed based on electro-acoustic combined detection method. This on-line monitoring system could synchronously detect two circuits' current signals caused by transformer PD: multiplex pulses and 6 circuits' ultrasonic signals. 12 core optical fiber transmission was used in hardware to suppress electromagnetic interference in field monitoring and improve the sensitivity of measurement; as well as the modular design method was adopted in software to improve the data rate and reliability of system operation. For the on-line operation of three transformers in the underground substation, the measured data show that the on-line monitoring system can detect PD signal of transformer on time, which can provide lots of creditable data for the condition-based maintenance of transformers.
transformer / acoustooptic combined detection / partial discharge / on-line monitoring / monitoring system
/
| 〈 |
|
〉 |