PDF(2347 KB)
Analysis of Transient Voltage-Frequency Coupling Mechanisms in Distribution Networks with Distributed Photovoltaic Integration
TANG Zhipeng, YIN Chunya, LI Fengting, LI Guangming, XIONG Li, LIU Wan
Electric Power Construction ›› 2026, Vol. 47 ›› Issue (2) : 161-173.
PDF(2347 KB)
PDF(2347 KB)
Analysis of Transient Voltage-Frequency Coupling Mechanisms in Distribution Networks with Distributed Photovoltaic Integration
[Objective] In response to the insufficient distribution network support and altered voltage-frequency coupling characteristics caused by the reduced inertia of the main grid due to large-scale renewable energy integration,this paper studies the transient voltage-frequency coupling mechanisms in distribution networks with distributed photovoltaic (DPV) integration. It aims to provide a theoretical basis for the development of an optimization and control strategy for the stable operation of distribution networks with high renewable energy penetration. [Methods] Based on the IEEE 33-bus system,the transient voltage and frequency response characteristics before and after DPV integration were analyzed. It was found that the dynamic coupling between voltage and frequency becomes more pronounced during renewable energy-dominated transients,with frequency issues being more critical under low-inertia conditions. The underlying causes of transient voltage sags and frequency fluctuations were explored,clarifying that the interaction between DPV and the network is a key factor in voltage-frequency coupling. From the perspective of power balance,the coupling mechanism between voltage and frequency during transients was elucidated by quantifying the dynamic relationship between active power variations in main grid and distribution networks. [Results] Simulations demonstrated that the transient response characteristics of DPV dominate voltage changes and further disturb frequency during transients. In low-inertia systems,the low-voltage ride-through (LVRT) process of DPV not only determines the voltage sag and recovery but also indirectly disturbs system frequency through its reactive power support. During transients,voltage changes alter the active power supply-demand relationship on the distribution network side,disrupting active power balance and leading to frequency fluctuations through power interactions between main grid and distribution networks. This clarifies the dominant path through which voltage changes disturb frequency. [Conclusion] This paper quantitatively describes the coupling relationship between voltage and frequency and reveals that the coupling mechanism is essentially a dynamic transmission process of "voltage fluctuation→active power imbalance→frequency response". The reactive-active power coupling characteristics of DPV exacerbate the complexity of voltage-frequency coupling. The clarification of this mechanism provides a theoretical basis for the development of voltage-frequency coordinated control strategies to suppress frequency fluctuations.
distribution network / voltage-frequency coupling / distributed photovoltaics(DPV) / low inertia / power balance / low voltage ride-through (LVRT) / coordinated control
| [1] |
王利平, 杨德洲, 张军. 大型光伏发电系统控制原理与并网特性研究[J]. 电力电子技术, 2010, 44(6): 61-63.
|
| [2] |
丁明, 王伟胜, 王秀丽, 等. 大规模光伏发电对电力系统影响综述[J]. 中国电机工程学报, 2014, 34(1): 1-14.
|
| [3] |
马宁宁, 谢小荣, 贺静波, 等. 高比例新能源和电力电子设备电力系统的宽频振荡研究综述[J]. 中国电机工程学报, 2020, 40(15): 4720-4732.
|
| [4] |
张曦, 张宁, 龙飞, 等. 分布式电源接入配网对其静态电压稳定性影响多角度研究[J]. 电力系统保护与控制, 2017, 45(6): 120-125.
|
| [5] |
曹文君, 张岩, 张安彬, 等. 弱电网条件下分布式光伏并网系统谐振机理及影响特性[J]. 电力建设, 2024(3): 149-159.
随着新型电力系统源网荷储协同一体化发展,分布式光伏并网规模的不断扩大,弱电网条件逐渐形成,同时多台逆变器接入配电网末端构成复杂阻抗网络,导致并网系统阻抗特性发生变化,同时增加了系统的谐振风险。为研究弱电网条件下分布式光伏并网系统谐振特征,通过建立系统等效阻抗模型分析关键参数对谐振特性的影响。首先,建立了计及电流内环、电容电流前馈、控制系统延时的逆变器诺顿等值模型。然后,考虑弱电网条件下公共耦合点(point of common coupling, PCC)处负荷特性对系统谐振的影响,构建了表征多并网逆变器、本地负荷、线路以及交流电网等关键设备阻抗交互耦合的分布式光伏并网系统等效模型;进一步,提出了反映逆变器谐波电流以及网侧背景谐波电压等多源谐波扰动对并网电流谐振激励作用的映射模型,揭示了电网阻抗、光伏输出功率、并网逆变器数量变化对系统谐振特性的影响规律。最后,通过仿真验证了所提光伏并网系统等效模型的准确性并分析了相关因素对光伏并网谐振特性的影响。
With the "source-grid-load-storage integration" and large-scale integration of distributed photovoltaic (PV), the grid condition is gradually presenting as a weak grid. Furthermore, multiple inverters are connected to the end of the distribution network to form a complex impedance network that increases the risk of resonance. To investigate the resonance mechanism of a distributed PV system under a weak grid, the Norton model of the inverter, considering the current loop, capacitive current feedforward, and control delay, is derived. Then, considering the influence of the load at the point of common coupling (PCC) on the system impedance characteristics under a weak grid, an equivalent model of a grid-connected system that can reveal the impedance matching relationship between multiple inverters, local loads, and the grid is established under weak grid conditions. Furthermore, a mapping model is proposed to reflect the excitation effect of the harmonic current of the inverter and the background harmonic voltage of the grid side on the resonance of the grid-connected current. The influence of the grid impedance, PV output power, and number of inverters on the resonance characteristics of the grid-connected system is revealed. Finally, the accuracy of the proposed equivalent model is verified through a simulation, and the influence of relevant factors on the PV grid-connected system is analyzed.
|
| [6] |
孙华东, 王宝财, 李文锋, 等. 高比例电力电子电力系统频率响应的惯量体系研究[J]. 中国电机工程学报, 2020, 40(16): 5179-5191.
|
| [7] |
|
| [8] |
蒋佳良, 晁勤, 陈建伟, 等. 不同风电机组的频率响应特性仿真分析[J]. 可再生能源, 2010, 28(3): 24-28.
|
| [9] |
文云峰, 杨伟峰, 林晓煌. 低惯量电力系统频率稳定分析与控制研究综述及展望[J]. 电力自动化设备, 2020, 40(9): 211-222.
|
| [10] |
袁小明, 张美清, 迟永宁, 等. 电力电子化电力系统动态问题的基本挑战和技术路线[J]. 中国电机工程学报, 2022, 42(5): 1904-1916.
|
| [11] |
|
| [12] |
刘万, 尹纯亚, 李凤婷, 等. 交流故障下光储弱电网电压波动传导路径及对频率变化影响分析[J]. 电网与清洁能源, 2025, 41(7): 107-115, 121.
|
| [13] |
栗峰, 丁杰, 周才期, 等. 新型电力系统下分布式光伏规模化并网运行关键技术探讨[J]. 电网技术, 2024, 48(1): 184-199.
|
| [14] |
刘运鑫, 姚良忠, 廖思阳, 等. 光伏渗透率对电力系统静态电压稳定性影响研究[J]. 中国电机工程学报, 2022, 42(15): 5484-5496.
|
| [15] |
韩璐, 尹纯亚, 戴晨, 等. 高比例新能源送端系统暂态电压运行风险分析[J]. 电力系统保护与控制, 2024, 52(1): 23-34.
|
| [16] |
徐艳春, 张婧宇, 张涛, 等. 基于两阶段特征选择的电力系统暂态功角与电压一体化稳定性评估方法[J]. 智慧电力, 2025, 53(4): 11-19.
|
| [17] |
张秀琦, 刘鸿清, 王立强, 等. 基于Koopman算子的新能源高占比电网暂态电压失稳识别方法[J]. 电力科学与技术学报, 2025, 40(2): 10-20, 41.
|
| [18] |
陈磊, 刘永奇, 戴远航, 等. 电力电子接口新能源并网的暂态电压稳定机理研究[J]. 电力系统保护与控制, 2016, 44(9): 15-21.
|
| [19] |
光伏发电系统接入配电网技术规定:GB/T29319—2024[S]. 北京: 中国标准出版社, 2024.
Technicalrequirementsforconnectingphotovoltaicpowersystemtodistributionnetwork:GB/T29319—2024[S]. Beijing: Standards Press of China, 42024.
|
| [20] |
光伏发电并网逆变器技术要求:GB/T37408—2019[S]. 北京: 中国标准出版社, 2019.
Technicalrequirementsforphotovoltaicgird-connectedinverter:GB/T37408—2019[S]. Beijing: Standards Press of China, 2019.
|
| [21] |
陈波, 朱晓东, 朱凌志, 等. 光伏电站低电压穿越时的无功控制策略[J]. 电力系统保护与控制, 2012, 40(17): 6-12.
|
| [22] |
|
| [23] |
韩民晓, 赵正奎, 郑竞宏, 等. 新能源场站电网暂态电压支撑技术发展动态[J]. 电网技术, 2023, 47(4): 1309-1322.
|
| [24] |
刘运鑫, 姚良忠, 廖思阳, 等. 分布式光储参与的直流受端近区配电网暂态电压控制方法[J]. 电网技术, 2023, 47(3): 1250-1261.
|
| [25] |
陈志伟, 汪杰, 向念文, 等. 基于新型混合变压器的配电网暂态电压稳定技术研究[J]. 电力科学与技术学报, 2025, 40(4): 282-293.
|
| [26] |
曹武, 杨铭, 胡波, 等. 基于构网变流器的新能源场站暂态电压分散协同控制策略[J]. 电力系统保护与控制, 2025, 53(14): 1-12.
|
| [27] |
徐衍会, 任晋, 田鑫, 等. 综合提升新能源高占比受端电网小干扰和暂态电压稳定性的SVG优化配置方法[J]. 电力系统保护与控制, 2024, 52(19): 119-130.
|
| [28] |
莫维科, 雷剑雄, 陈亦平, 等. 典型独立同步电网新能源高渗透率运行中的频率稳定挑战与应对措施(上)[J]. 电力系统保护与控制, 2025, 53(16): 177-187.
|
| [29] |
高丙团, 胡正阳, 王伟胜, 等. 新能源场站快速有功控制及频率支撑技术综述[J]. 中国电机工程学报, 2024, 44(11): 4335-4352.
|
| [30] |
辛保安, 李明节, 贺静波, 等. 新型电力系统安全防御体系探究[J]. 中国电机工程学报, 2023, 43(15): 5723-5731.
|
| [31] |
汪梦军, 郭剑波, 马士聪, 等. 新能源电力系统暂态频率稳定分析与调频控制方法综述[J]. 中国电机工程学报, 2023, 43(5): 1672-1693.
|
| [32] |
张怡, 张恒旭, 李常刚, 等. 电力系统频率响应模式及其量化描述[J]. 中国电机工程学报, 2021, 41(17): 5877-5886.
|
| [33] |
刘印, 陈民权, 李京, 等. 电力系统低频减载的单调控制特性[J]. 电力自动化设备, 2023, 43(7): 182-189.
|
| [34] |
钟诚, 周顺康, 严干贵, 等. 基于变减载率的光伏发电参与电网调频控制策略[J]. 电工技术学报, 2019, 34(5): 1013-1024.
|
| [35] |
张磊光, 陈海涛, 吴赋章, 等. 基于可学习模型预测控制的含风电多微网频率控制方法[J]. 智慧电力, 2024, 52(10): 49-55, 87.
|
| [36] |
徐鹏, 郭新元, 赵伟, 等. 功率与频率耦合下100%新能源电力系统的潮流分析模型[J]. 智慧电力, 2024, 52(12): 73-79, 87.
|
| [37] |
邹世豪, 曹永吉, 刘志文, 等. 计及多时间尺度电压失稳模式的电网薄弱环节辨识[J]. 电力系统保护与控制, 2024, 52(21): 35-49.
|
| [38] |
李逸欣, 吴伟杰, 张伊宁, 等. 大规模新能源接入的电力系统惯量缺失机理及惯量水平评估[J]. 南方能源建设, 2024, 11(5): 132-139.
|
| [39] |
张恒旭, 高志民, 曹永吉, 等. 高比例可再生能源接入下电力系统惯量研究综述及展望[J]. 山东大学学报(工学版), 2022, 52(5): 1-13.
|
| [40] |
分布式电源接入电网承载力评估导则:DL/T2041—2019[S]. 北京: 中国电力出版社, 2019.
Technicalguidelineforevaluatingpowergridhostingcapacityofdistributedresourcesconnectedtonetwork:DL/T2041—2019[S]. Beijing: China Electric Power Press, 2019.
|
| [41] |
龚锦霞, 解大, 张延迟. 三相数字锁相环的原理及性能[J]. 电工技术学报, 2009, 24(10): 94-99, 121.
|
/
| 〈 |
|
〉 |