Forward Traveling Wave Pilot Protection for Renewable Energy Outgoing Lines Based on Post-Test Simulation Principle

SHI Hengchu, WANG Hongyu, LEI Shunguang, CHEN Xiaofan, LI Yinyin, YOU Hao, ZHOU Haicheng, SHU Hongchun

Electric Power Construction ›› 2026, Vol. 47 ›› Issue (10) : 62-74.

PDF(1431 KB)
PDF(1431 KB)
Electric Power Construction ›› 2026, Vol. 47 ›› Issue (10) : 62-74. DOI: 10.12204/j.issn.1000-7229.2026.10.005
Dispatch & Operation

Forward Traveling Wave Pilot Protection for Renewable Energy Outgoing Lines Based on Post-Test Simulation Principle

Author information +
History +

Abstract

[Objective] Against the background of large-scale renewable energy integration,the fault currents of renewable energy sources exhibit characteristics such as limited amplitude,frequency offset,and phase distortion. This leads to the insufficient adaptability of traditional power-frequency phasor-based protection,making it prone to maloperation or failure to operate. To address this issue,a forward traveling wave pilot protection method based on the post-test simulation principle is proposed. [Methods] Firstly,an analysis of the fault characteristics of renewable energy sources reveals that the fault current characteristics of full-power converter-interfaced sources and doubly-fed induction generators are significantly different from those of traditional synchronous generators,which leads to the poor adaptability of traditional protection. Secondly,the post-test simulation protection principle is proposed,and the voltage and current equations of lossless transmission lines are derived. On this basis,considering the resistance loss of practical lines,the expressions of simulated voltage and current are defined to calculate the quantities from the protection terminals to any internal point of the line. Finally,taking the line midpoint as the simulation point,the simulated forward voltage traveling waves extrapolated from both ends to the midpoint are calculated,and fault identification is achieved based on the waveform differences between internal and external faults. [Results] A simulation model of the wind-PV-storage transmission system is built in PSCAD/EMTDC to verify the applicability of the proposed protection. The results show that the proposed protection requires only a 2 ms data window for fault identification,can tolerate a transition resistance of up to 300 Ω and white-noise interference at a signal-to-noise ratio of 30 dB,and exhibits good adaptability to variations in renewable energy output. [Conclusions] The proposed method is a transient-quantity-based protection method that does not rely on power-frequency phasors and fault current amplitudes. It effectively avoids the adverse impacts of renewable energy fault characteristics on traditional protection,demonstrates good comprehensive performance and engineering applicability,and is suitable for pilot protection of renewable energy outgoing lines.

Key words

large-scale renewable energy / outgoing line / pilot protection / post-test simulation principle / traveling wave

Cite this article

Download Citations
SHI Hengchu , WANG Hongyu , LEI Shunguang , et al . Forward Traveling Wave Pilot Protection for Renewable Energy Outgoing Lines Based on Post-Test Simulation Principle[J]. Electric Power Construction. 2026, 47(10): 62-74 https://doi.org/10.12204/j.issn.1000-7229.2026.10.005

References

[1]
张政伟, 陈谦, 牛应灏, 等. 基于实时生成定值的高比例新能源电网自适应电流保护[J]. 电力建设, 2024, 45(2): 137-146.
Abstract
新型电力系统电源侧含有高比例新能源电源,受其状态多样性、布置分散性、输出非线性等影响,电网故障期间短路电流水平下降且不确定性增强,给传统电流保护的整定配合造成困难。为此,结合传统三段式电流保护,提出了一种基于实时生成定值的自适应电流保护方法。该方法计及新能源实际故障输出而生成定值,包括:首先,建立能区分新能源和发电机不同输出特性的等效电源模型,故障前对短路前后不变的模型参数持续辨识;故障发生后,结合就地测量信息获取等效电源模型的变化参数;然后,基于实际故障场景和故障期间新能源实际输出,对分段式电流保护进行实时整定;最后,结合测量值与整定值进行动作判断。故障前的持续辨识,保证了发电机与新能源的有效分离;基于实际故障场景生成定值可计及新能源的整体输出作用,有效应对其分散性、多样性与非线性问题。通过算例对比与分析,验证了所提自适应电流保护方法的可行性与正确性。
Zhang Zhengwei, Chen Qian, Niu Yinghao, et al. Real-time generated protection settings based adaptive current protection for transmission line considering high proportion of new energy source[J]. Electric Power Construction, 2024, 45(2): 137-146.

The power sides of new power systems contain a large proportion of new energy sources. Owing to various types, distributed locations, and nonlinear outputs, the through-current level of the short circuit decreases, and its uncertainty increases when a fault occurs in the power grid, which makes it difficult for traditional current protection to preset and trip. Therefore, an adaptive current protection method based on real-time generated settings using local information is proposed, referring to traditional three-stage current protection. This method considers the actual fault characteristics of new energy sources to generate a preset. First, an equivalent source model is established that can distinguish the different outputs of new energy sources between generators and identify them online to obtain the unchanged parameters before and after the fault. Then, after a fault occurs, the local measured information is used to obtain the changeable parameters. Subsequently, preset values were generated in real-time based on the actual fault scenario and the actual output of new energy sources during the fault. Finally, the trip is decided based on the measured current and the preset value. Continuous identification before a fault occurs can effectively separate generators and new energy sources in the model. Online presetting based on actual fault scenarios and the output of new energy sources can effectively solve the problems of variety, distribution, and nonlinearity. The feasibility and correctness were verified by both analysis and comparison of various cases.

[2]
孙丽华. 基于双碳背景的高比例可再生能源电力系统[J]. 中国科技信息, 2023(14): 117-119.
Sun Lihua. High proportion renewable energy power system based on double carbon background[J]. China Science and Technology Information, 2023(14): 117-119.
[3]
司俊龙, 艾琳, 邱辰. 2023年中国光伏发电发展现状与展望[J]. 水力发电, 2024, 50(11): 1-4.
Si Junlong, Ai Lin, Qiu Chen. Status and prospect of China's photovoltaic power development in 2023[J]. Water Power, 2024, 50(11): 1-4.
[4]
李耀, 高昆, 江华, 等. 2024年全球光伏市场进展概述[J]. 太阳能, 2025(12): 5-11.
Li Yao, Gao Kun, Jiang Hua, et al. Overview of global pv market development in 2024[J]. Solar Energy, 2025(12): 5-11.
[5]
Ashraf A, Sagheer M. Renewable energy capacity and technological innovations: a review of global trends and future directions[J]. Environmental Progress & Sustainable Energy, 2025, 44(6): e70071.
[6]
刘轶, 王景钢. 大型光伏电站并网暂态特性研究[J]. 电力系统保护与控制, 2021, 49(7): 182-187.
Liu Yi, Wang Jinggang. Analysis of transient characteristics when large-scale photovoltaics are connected to a power system[J]. Power System Protection and Control, 2021, 49(7): 182-187.
[7]
Du B W, Guo H Y, Jiang T. Two-stage short circuit current method based on new energy source fault characteristic fitting[J]. Journal of Physics: Conference Series, 2023, 2564(1): 012050.
[8]
高淑萍, 蔚坤, 宋国兵, 等. 适用于双馈风电场送出线的纵联方向保护研究[J]. 太阳能学报, 2024, 45(1): 218-225.
Abstract
考虑风电场接入电网时,传统方向元件在短路故障发生时易受到风电场内部电力电子器件动态特性的干扰影响,导致频率特性偏移,系统参数不稳定和弱馈性等问题,使继电保护装置不能及时或正确判断故障发生区域。针对上述问题,首先对含有风电场的故障附加网络进行分析,寻找故障发生后纵联保护安装处各测量点电气量之间的关联性,确定其故障逻辑关系。其次通过对常用的相模变换解耦方式进行分析,选择一个合理的方法代入相关性表达式,根据相关系数值完成故障区域判定。最后利用PSCAD/EMTDC搭建双馈风电场并网模型,设置各种不同的故障类型和场景,并利用Matlab进行保护算法验证,检验故障区域判断结果,验证所提保护方法的正确性与合理性,并且仿真结果表明该方法具有较高的可靠性。
Gao Shuping, Yu Kun, Song Guobing, et al. Research on pilot direction protection suitable for doubly-fed wind farm outgoing line[J]. Acta Energiae Solaris Sinica, 2024, 45(1): 218-225.
When the wind farm is connected to the power grid, the traditional directional element is susceptible to the interference of the dynamic characteristics of the power electronic devices inside the wind farm when the short-circuit fault occurs, which leads to the frequency characteristic deviation, system parameter instability and weak feedability, so that the relay protection device cannot judge the fault area timely or correctly. In order to solve the above problems, the fault additional network containing wind farms is analyzed first, and the correlation between the electrical quantities of each measurement point at the pilot protection installation after the fault occurs is found, and the fault logic relationship is determined. Then, through the analysis of the common decoupling mode of phase-mode transformation, a reasonable method is selected to replace the correlation expression, and the fault region is determined according to the correlation coefficient value. Finally, PSCAD/EMTDC is used to build the doubly-fed wind farm grid-connected model and various fault types and scenarios are set. Matlab is used to verify to test the judgment results of the fault area to determine the correctness and rationality of the proposed method. Simulation results show that this method has high reliability.
[9]
黄强, 李宽, 范荣奇, 等. 新能源直流送出系统受端交流故障穿越控制策略[J]. 电力工程技术, 2025, 44(6): 165-173.
Huang Qiang, Li Kuan, Fan Rongqi, et al. A grid side fault ride-through control for renewable energy connected MMC-HVDC[J]. Electric Power Engineering Technology, 2025, 44(6): 165-173.
[10]
Jia K, Gu C J, Xuan Z W, et al. Fault characteristics analysis and line protection design within a large-scale photovoltaic power plant[J]. IEEE Transactions on Smart Grid, 2018, 9(5): 4099-4108.
[11]
李振兴, 杨梓康, 杨桄, 等. 大规模新能源送出线路继电保护关键技术探讨[J]. 浙江电力, 2025, 44(10): 10-26.
Li Zhenxing, Yang Zikang, Yang Guang, et al. Key technologies for relay protection of bulk renewable energy transmission lines[J]. Zhejiang Electric Power, 2025, 44(10): 10-26.
[12]
徐健, 王飞, 马楠. 新能源接入背景下继电保护适应性分析与改进[J]. 电力设备管理, 2025(17): 169-171.
Xu Jian, Wang Fei, Ma Nan. Adaptability analysis and improvement of relay protection under the background of new energy access[J]. Electric Power Equipment Management, 2025(17): 169-171.
[13]
晁晨栩, 郑晓冬, 高飘, 等. 针对光伏场站送出线路不对称短路故障的自适应距离保护原理[J]. 中国电机工程学报, 2022, 42(18): 6681-6692.
Chao Chenxu, Zheng Xiaodong, Gao Piao, et al. Adaptive distance protection for transmission line of photovoltaic station during asymmetric short circuit[J]. Proceedings of the CSEE, 2022, 42(18): 6681-6692.
[14]
申洪明, 肖智宏, 刘颖, 等. 电力电子化背景下交流电网保护配置方案[J]. 电力建设, 2020, 41(7): 75-81.
Abstract
大量电力电子器件的应用使得交流系统的故障特性发生了较大变化,现有保护配置方案面临严峻挑战。首先分析了纯交流系统、直流输电系统、新能源并网等不同场景下交流线路故障暂态电流波形特征,进而利用相关系数进行暂态电流波形辨识,构建了新型保护原理与配置方案。最后,分析了新型保护方案对互感器、采样频率、数据窗长的配置要求。新型保护配置方案普适性强,出口速度快,实现简单。基于EMTDC/PSCAD仿真与样机测试结果验证了分析结论的正确性。
Shen Hongming, Xiao Zhihong, Liu Ying, et al. Research on AC protection scheme under the background of power electronics[J]. Electric Power Construction, 2020, 41(7): 75-81.
The application of a lot of power electronic equipment has caused a large change in the fault characteristics of the AC system, and the existing protection schemes faces greater challenge. This paper firstly analyzes the waveform characteristics of AC line fault current in different fault scenarios, such as pure AC systems, DC transmission systems and new energy grid-connection, and then a new protection scheme based on identification of transient current spectrum is proposed. At last, the effect of current transformer, sampling frequency and data window length is analyzed. The new protection scheme has many application scenarios, fast operation, and simple implementation. The conclusions are verified by the simulation results of EMTDC / PSCAD and prototype test.
[15]
史雷敏, 惠杰, 田宝江, 等. 不同控制背景下的新能源集中送出线路保护适应性分析[J]. 电网与清洁能源, 2024, 40(12): 120-127.
Shi Leimin, Hui Jie, Tian Baojiang, et al. Adaptability analysis of protection for new energy centralized feeders under different control backgrounds[J]. Power System and Clean Energy, 2024, 40(12): 120-127.
[16]
温志文, 贾科, 余磊, 等. 基于时频特性相似度的新能源场站T接型送出线路高速保护[J]. 电力系统保护与控制, 2023, 51(4): 1-11.
Wen Zhiwen, Jia Ke, Yu Lei, et al. High speed protection based on time-frequency characteristic similarity for a Teed transmission line connected to renewable energy power plants[J]. Power System Protection and Control, 2023, 51(4): 1-11.
[17]
贾科, 杨哲, 朱正轩, 等. 基于电流幅值比的逆变型新能源场站送出线路T接纵联保护[J]. 电力自动化设备, 2019, 39(12): 82-88.
Jia Ke, Yang Zhe, Zhu Zhengxuan, et al. Pilot protection based on current amplitude ratio for teed line in inverter-interfaced renewable energy power plants[J]. Electric Power Automation Equipment, 2019, 39(12): 82-88.
[18]
叶远波, 章昊, 王同文, 等. 基于电压行波极性特征的新能源送出线路保护方案[J]. 电力工程技术, 2024, 43(1): 127-135.
Ye Yuanbo, Zhang Hao, Wang Tongwen, et al. Renewable energy line protection based on voltage traveling wave polarity[J]. Electric Power Engineering Technology, 2024, 43(1): 127-135.
[19]
Yang Z, Liao W L, Wang H Y, et al. Improved euclidean distance based pilot protection for lines with renewable energy sources[J]. IEEE Transactions on Industrial Informatics, 2022, 18(12): 8551-8562.
[20]
王兴国, 周泽昕, 程琪. 新能源送出线路高灵敏序电流差动保护[J]. 浙江电力, 2025, 44(10): 27-37.
Wang Xingguo, Zhou Zexin, Cheng Qi. A highly sensitive sequence-current differential protection method for grid-connected renewable energy transmission lines[J]. Zhejiang Electric Power, 2025, 44(10): 27-37.
[21]
王少雄, 吕思辰, 吕飞鹏, 等. 基于Fréchet距离的集中式光伏场站送出线路纵联保护方法[J]. 电网技术, 2025, 49(4): 1648-1657.
Wang Shaoxiong, Lü Sichen, Lü Feipeng, et al. Fréchet distance based pilot protection method for centralized photovoltaic station transmission lines[J]. Power System Technology, 2025, 49(4): 1648-1657.
[22]
Zheng L M, Jia K, Bi T S, et al. Cosine similarity based line protection for large-scale wind farms[J]. IEEE Transactions on Industrial Electronics, 2021, 68(7): 5990-5999.
[23]
Chen L, Lin X N, Li Z T, et al. Similarity comparison based high-speed pilot protection for transmission line[J]. IEEE Transactions on Power Delivery, 2018, 33(2): 938-948.
[24]
邓力川, 吴浩, 李小鹏. 基于Kendall相关系数的新能源场站送出线路纵联保护[J]. 四川轻化工大学学报(自然科学版), 2025, 38(6): 69-78.
Deng Lichuan, Wu Hao, Li Xiaopeng. Pilot protection of new energy station transmission line based on Kendall correlation coefficient[J]. Journal of Sichuan University of Science & Engineering (Natural Science Edition), 2025, 38(6): 69-78.
[25]
李振兴, 杨桄, 王莉, 等. 基于多模态分解信息的新能源场站送出线路纵联保护新判据[J]. 电力系统保护与控制, 2026, 54(3): 22-34.
Li Zhenxing, Yang Guang, Wang Li, et al. A new pilot protection criterion for renewable energy outgoing lines based on multimodal decomposition information[J]. Power System Protection and Control, 2026, 54(3): 22-34.
[26]
马冰清, 李振兴. 考虑电流限幅的构网型光伏场站送出线路纵联保护新原理[J]. 中国电力, 2025, 58(8): 164-175.
Ma Bingqing, Li Zhenxing. A new pilot protection for transmission lines based on overcurrent limiting from grid-forming power sources[J]. Electric Power, 2025, 58(8): 164-175.
[27]
李铁成, 范辉, 张卫明, 等. 基于5G通信的有源配电网新能源送出线路纵联保护[J]. 中国电力, 2024, 57(11): 139-150.
Li Tiecheng, Fan Hui, Zhang Weiming, et al. Pilot protection of new energy transmission line in active distribution network based on 5G communication[J]. Electric Power, 2024, 57(11): 139-150.
[28]
戴志辉, 韦舒清, 柳梅元. 新能源送出线路工频变化量距离保护不正确动作机理分析[J]. 电力系统保护与控制, 2025, 53(6): 74-86.
Dai Zhihui, Wei Shuqing, Liu Meiyuan. Analysis of the incorrect operation mechanism of power frequency variation-based distance protection in new energy transmission lines[J]. Power System Protection and Control, 2025, 53(6): 74-86.
[29]
王兴国, 柳焕章, 吕鹏飞, 等. 新能源送出线路两相接地故障距离保护动作差异机理分析及对策[J/OL]. 电网技术,2026-03-16. https://doi.org/10.13335/j.1000-3673.pst.2025.0567.
Wang Xingguo, Liu Huanzhang, Lyu Pengfei, et al. Mechanism analysis of distance protection different actions for two phase ground faults in grid-connected renewable energy transmission lines and countermeasures[J/OL]. Power System Technology,2026-03-16. https://doi.org/10.13335/j.1000-3673.pst.2025.0567.
[30]
杨国生, 王润良, 王聪博, 等. 基于负序抑制策略特性的新能源送出线路距离保护原理[J]. 电网技术, 2026, 50(4): 1719-1728.
Yang Guosheng, Wang Runliang, Wang Congbo, et al. Distance protection principle for renewable energy transmission lines based on negative sequence suppression strategy characteristics[J]. Power System Technology, 2026, 50(4): 1719-1728.
[31]
Saleh K A, Allam M A. Synthetic harmonic distance relaying for inverter-based islanded microgrids[J]. IEEE Open Access Journal of Power and Energy, 2021, 8: 258-267.
[32]
Yang Z, Zhang Q, Liao W L, et al. Harmonic injection based distance protection for line with converter-interfaced sources[J]. IEEE Transactions on Industrial Electronics, 2023, 70(2): 1553-1564.
[33]
韩一鸣, 束洪春, 达慧, 等. 基于测后模拟原理的半波长输电线路暂态量纵联保护[J]. 电机与控制学报, 2021, 25(3): 115-124.
Han Yiming, Shu Hongchun, Da Hui, et al. Transient longitudinal protection of half-wavelength transmission line based on post-test simulation principle[J]. Electric Machines and Control, 2021, 25(3): 115-124.
[34]
束洪春, 高峰, 葛耀中, 等. 辐射状馈线故障测距的测后模拟法[J]. 电网技术, 2000, 24(6): 50-54.
Shu Hongchun, Gao Feng, Ge Yaozhong, et al. Simulation after test method for fault location of radial feeder[J]. Power System Technology, 2000, 24(6): 50-54.
[35]
束洪春, 彭仕欣, 李斌, 等. 基于零序电流激励的谐振接地系统故障选线测后模拟方法[J]. 电工技术学报, 2008, 23(10): 106-113.
Shu Hongchun, Peng Shixin, Li Bin, et al. Simulation after detecting fault line in resonant earthed system through zero sequence current motivation[J]. Transactions of China Electrotechnical Society, 2008, 23(10): 106-113.
[36]
束洪春, 彭仕欣, 李斌, 等. 利用测后模拟的谐振接地系统故障选线方法[J]. 中国电机工程学报, 2008, 28(16): 59-64.
Shu Hongchun, Peng Shixin, Li Bin, et al. A new approach to detect fault line in resonant earthed system using simulation after test[J]. Proceedings of the CSEE, 2008, 28(16): 59-64.
[37]
郑黎明, 贾科, 毕天姝, 等. 基于结构相似度与平方误差的新能源场站送出线路纵联保护综合判据[J]. 电网技术, 2020, 44(5): 1788-1795.
Zheng Liming, Jia Ke, Bi Tianshu, et al. Comprehensive criteria of pilot protection based on structural similarity and square error for outgoing line from renewable power plants[J]. Power System Technology, 2020, 44(5): 1788-1795.
[38]
Chang Z X, Song G B, Wang T. Analysis on current characteristics of PMSG under grid three-phase fault[J]. The Journal of Engineering, 2018, 2018(15): 785-790.
[39]
Sulla F, Svensson J, Samuelsson O. Symmetrical and unsymmetrical short-circuit current of squirrel-cage and doubly-fed induction generators[J]. Electric Power Systems Research, 2011, 81(7): 1610-1618.
[40]
郭壮志, 孔繁镍, 徐其兴. 电力系统相模变换矩阵的最优化建模方法[J]. 电力自动化设备, 2023, 43(11): 166-173.
Guo Zhuangzhi, Kong Fannie, Xu Qixing. Optimization method for modeling phase-mode transformation matrix of power system[J]. Electric Power Automation Equipment, 2023, 43(11): 166-173.
[41]
王艳婷, 樊顺跃, 刘乐, 等. 基于频域能量比值的柔性直流输电线路单端量高可靠性保护方案[J]. 电力系统保护与控制, 2025, 53(20): 1-10.
Wang Yanting, Fan Shunyue, Liu Le, et al. High-reliability non-unit protection for flexible DC transmission lines based on frequency-domain energy ratio[J]. Power System Protection and Control, 2025, 53(20): 1-10.
[42]
Gao X P, Song G B, Kang X N, et al. Pilot protection based on backward traveling-wave voltage difference for submarine cables of low-frequency transmission system with integrated offshore wind power[J]. Journal of Modern Power Systems and Clean Energy, 2025, 13(4): 1176-1187.

Footnotes

利益冲突声明(Conflict of Interests): 所有作者声明不存在利益冲突。

作者贡献声明(Authors' Contributions): 石恒初完成论文撰写;王鸿宇开展理论推导和仿真分析;雷顺广参与方案设计并修改论文;陈晓帆参与论文修改;李银银整理仿真数据;游昊验证保护方案;周海成收集相关资料;束洪春提出研究思路并指导论文写作。所有作者均阅读并同意了论文终稿内容。

Funding

National Natural Science Foundation of China(52037003)
Science and Technology Project of China Southern Power Grid Co.,Ltd.(YNKJXM20240531)
Yunnan Fundamental Research Projects(202401BE070001-014)
PDF(1431 KB)

Accesses

Citation

Detail

Recommended

/

〈 〉