Influence Factors of Fitting on Grip Strength of Large Cross-section Conductor

Electric Power Construction ›› 2012, Vol. 33 ›› Issue (6) : 84-88.

PDF(3001 KB)
PDF(3001 KB)
Electric Power Construction ›› 2012, Vol. 33 ›› Issue (6) : 84-88.

Influence Factors of Fitting on Grip Strength of Large Cross-section Conductor

Author information +
History +

Abstract

Jinping-Sunan ±800 kV UHV DC line uses hydraulic splicing fitting and strain clamp, and the grip strength of fitting should be more than 95 % RTS. Because 900 mm2 large cross-sections ACSR was 4-layer aluminum stranded structure, especially the aluminum/steel ratio of JL/G3A-900/40 conductor was larger, this paper mainly studied the influence factors of fitting on the grip strength of large cross-section conductor. The result shows that there is a wire strength loss caused by crimping, which is the main influence factor, as well as aluminum /steel ratio.

Key words

900 mm2 large cross-section conductor / crimping retention rate / wire strength / aluminum/steel ratio

Cite this article