• CSCD核心库收录期刊
  • 中文核心期刊
  • 中国科技核心期刊

ELECTRIC POWER CONSTRUCTION ›› 2015, Vol. 36 ›› Issue (5): 31-36.doi: 10.3969/j.issn.1000-7229.2015.05.006

Previous Articles     Next Articles

Failure Analysis and Protection Strategy for MMC-UPQC

LU Jingjing1, LIU Zhengfu2, ZHANG Jian1, YUAN Chang1, XIAO Xiangning1, YANG Yongchun1   

  1. 1. State Key Laboratory of Alternate Electrical Power System with Renewable Energy Sources of North China Electric Power University, Beijing 102206, China;2. Electric Power Research Institute of Guangdong Power Grid Corporation, Guangzhou 510080, China
  • Online:2015-05-01
  • Supported by:

    Project Supported by Key Project of the National Tewlfth-Five Year Research Program of China (2011BAA01B02)

Abstract:

Applying the topology structure of modular multilevel converter (MMC) in unified power quality controller (UPQC) can improve the applicative capacity and voltage level of UPQC, which can expand the application of UPQC in medium voltage field, and make UPQC has wider application prospects. However, when the short-circuit fault occurs on the load side, how to logically operate to ensure the safe and reliable operation of UPQC, is not only the system requirement for the device, but also its own requirement for the device to protect itself. On this basis, this paper presented the principle of fault protection strategy for MMC-UPQC, which adopts the interaction between the branch of anti-parallel thyristor and circuit breaker to isolate the MMC in series from the fault line, and ensure the effective protection for the device. The simulation results in PSCAD/EMTDC environment have demonstrated the effectiveness and feasibility of the proposed method.

Key words: unified power quality conditioner (UPQC), modular multilevel converter (MMC), fault protection, circuit breaker, anti-parallel thyristor